A detail was given to us by a contractor wanting to use ADOT’s front face barrier transition for adding light poles on top of barrier in lieu of MoDOT’s standard where no transition on front face is required since it (ADOT’s) will allow for slip forming the barrier.
Our barrier will be 42” tall (Type D single sloped 11%) without a light pedestal added.
Is ADOT’s detail with 5’ front face transitions from a sloped face to a vertical face at the light pole using MoDOT’s 42” barrier without a light pedestal is an acceptable detail and if not how can we make it an acceptable detail?
1st sheet of attachment – ADOT’s detail with 33” barrier and top mounted pedestal
2nd sheet of attachment – MoDOT’s standard lighting blister
I would appreciate your comments. Thx.
For lateral tapers on the front face of concrete barriers, we have started to suggest the use of a 1:10 (lateral to longitudinal) when the shape transition extends over a larger vertical footprint. Note that this suggestion was solely based on LS-DYNA simulations involving vehicle impacts into a lateral shape transitions on rigid concrete buttresses. Full-scale crash testing has not been performed to confirm nor modify these simulation findings.
Previously, MwRSF conducted limited crash testing on luminaire poles attached to 32-in. tall single-slope parapets under TL-4 impacts using NCHRP Report No. 350. A link to the report and crash videos is provided below:
https://mwrsf.unl.edu/reportresult.php?reportId=104&search-textbox=zoi
Are you considering the configuration under MASH TL-3 or TL-4? Also, I would need to see the CAD details to further comment (not attached in prior email). Thanks!