We are putting in the side mounted weak post MGS system. Contractor snapped off one of the bolts on the bottom connection. Got any ideas how to “fix” this.
I have two potential options.
1. You can drill out the broken anchor and install a Hilti HISN threaded insert with an equivalent bolt. We do this with the SAFER Barrier when we damage an anchor.
2. You could replace the post attachment bracket with a modified one that has a longer lower-left steel tab. The tab could be lengthened by 2" such that a new anchor could be installed without interfering with the original.